Product Detail
Technical overview, positioning and application information for this product.
Need Technical Support?
Use the inquiry form to request datasheets, pricing or delivery consultation.
UL Fire Alarm Cable FPLR
Short Description
UL certified FPLR fire alarm cable for vertical shaft and multi-floor installations. 300V rating, 2-8 cores. Flame retardant PVC insulation and sheath.
Technical Parameters
Voltage Rating300V
Temperature Limits-20°C to +105°C
Min Bending Radius10-15 times cable outer diameter
Flame Propagation (Multiple cables)UL1666
Flame Propagation (single Insulation)UL2556
Flame spread of single core cableUL1581
Fire Resistance Time30 minutes
Product Description
Product Overview
Type FPLR (Fire Power Limited Rated) cable designed for vertical runs in shafts and multi-floor installations per NEC section 760-154(B). Certified for fire alarm circuits requiring enhanced fire performance.
Applications: Vertical shaft installations, multi-floor fire alarm systems, fire detection and signaling circuits, emergency communication systems.
Construction
| Component | Specification |
|---|---|
| Conductor | 25AWG-12AWG per UL 1581 |
| Insulation | Flame retardant PVC |
| Circuit Protective Conductor | Tinned Copper |
| Overall Screen | AL/PET (Aluminium/Polyester Tape) |
| Sheath | Flame retardant PVC |
Standards Certified
- UL 1581 Standard
- UL1666 Flame Propagation
- UL2556 Single Cable Test
Related Products